New
ACV E-Tech P High-Output Three-Phase Electric Boiler
ACV E-Tech P electric boiler
The ACV E-Tech P is a high-output, floor-standing three-phase electric boiler designed for commercial buildings, industrial heating systems, large properties and applications requiring substantial electrical heating capacity.
The E-Tech P range is available in five output levels: 57.6kW, 115.2kW, 144kW, 201.6kW and 259.2kW. Each model uses a 400V three-phase power supply and can provide staged heating control to match the required load.
With no combustion process and no flue requirement, the ACV E-Tech P can be considered where a high-output electric heating solution is required and suitable three-phase electrical infrastructure is available.
Key Features about ACV E-Tech P
- High-output three-phase electric boiler
- Floor-standing design
- Available from 57.6kW to 259.2kW
- 400V three-phase power supply
- Four-stage power control
- Electronic sequencing control
- Can be used as a primary heating source
- Suitable for emergency or backup heating
- Can be installed in multiple-boiler configurations
- Stainless steel Incoloy 800 heating elements
- Integrated control panel
- Thermostat and temperature indication
- Power-level indicators
- Manual high-limit temperature protection
- Minimum water-pressure warning
- Maximum operating temperature of 90°C
- Maximum heating-system operating pressure of 4 bar
- Low-maintenance design
- No combustion flue required
ACV specifies stainless steel Incoloy 800 heating elements, four-stage electronic sequencing and a 400V three-phase power circuit with a separate 230V single-phase control circuit.
ACV E-Tech P Models
| Model | Maximum Output | Minimum Output | Heating Elements |
|---|---|---|---|
| E-Tech P 57 | 57.6kW | 14.4kW | 2 |
| E-Tech P 115 | 115.2kW | 28.8kW | 4 |
| E-Tech P 144 | 144kW | 36.0kW | 5 |
| E-Tech P 201 | 201.6kW | 50.4kW | 7 |
| E-Tech P 259 | 259.2kW | 64.8kW | 9 |
The exact staged power configuration varies by model. ACV documentation confirms the five model range and the corresponding electrical outputs.
Four-Stage Electric Heating Control
The ACV E-Tech P uses an electronic sequencing controller with four-stage modulation. The system progressively brings heating stages into operation according to the required heat demand.
The maximum power can also be limited to 25%, 50% or 75% using the manufacturer’s specified configuration method.
This makes the E-Tech P suitable for heating systems where controlled staged electrical output is required rather than a simple single-stage electric heat source.
Commercial and Industrial Heating Applications
The ACV E-Tech P can be considered for applications such as:
- Commercial buildings
- Large residential properties
- Apartment buildings
- Schools and educational facilities
- Healthcare facilities
- Industrial buildings
- Workshops and production facilities
- Warehouses
- Large offices
- Backup and emergency heating systems
- Gas-free heating installations
- Multiple-boiler heating systems
The appropriate model should be selected according to the building heat-loss calculation, hydraulic design and available electrical capacity.
Three-Phase Electric Boiler for Large Heating Systems
The E-Tech P is specifically designed for installations where substantial electrical heating output is required.
The models use 3 × 400V three-phase electrical power, while the control circuit uses 230V single-phase power. Electrical demand is substantial, particularly on the higher-output models, so the installation must be designed around the manufacturer’s electrical specifications and the site’s available supply.
Heating System Compatibility
ACV states that the E-Tech P is suitable for connection to most sealed heating and hot-water systems, with a maximum working pressure of 4 bar and maximum temperature of 90°C. It can also be connected to external storage cylinders for domestic hot-water production where the system is designed for this purpose.
E-Tech P Heating Elements
The boiler uses removable stainless steel Incoloy 800 heating elements mounted from the front of the heating body.
The heating body is constructed from mild steel and is hydraulically tested before operation. The maximum operating pressure is 4 bar.
Installation Requirements
The ACV E-Tech P is a commercial-scale electrical heating appliance and should be specified and installed by appropriately qualified heating and electrical professionals.
Before purchasing, confirm:
- Required boiler output
- Building heat-loss calculation
- Available three-phase electrical supply
- Electrical protection requirements
- Hydraulic system design
- Heating-system operating pressure
- Pipework and connection requirements
- Plant-room access and dimensions
- Local electrical regulations
- Local heating and building regulations
- Whether additional system controls are required
ACV documentation specifies that the boiler’s power circuit operates at 400V three-phase and that the control circuit operates at 230V single phase.
Important Frost Protection Information
The E-Tech P is not fitted with integral frost protection. ACV recommends a suitable external frost thermostat where the boiler is installed in a location where freezing may occur.
ACV E-Tech P Technical Specifications
Product: ACV E-Tech P
Type: Floor-standing electric boiler
Heating type: Heat only
Models: 57, 115, 144, 201 and 259
Maximum output: 57.6–259.2kW
Electrical supply: 3 × 400V
Control supply: 1 × 230V
Frequency: 50/60Hz
Control: Four-stage electronic sequencing
Maximum operating temperature: 90°C
Maximum heating pressure: 4 bar
Heating elements: Stainless steel Incoloy 800
Installation: Floor standing
Multiple boiler installation: Supported
ACV’s current documentation confirms these core technical characteristics across the E-Tech P range.
Frequently Asked Questions
What is the ACV E-Tech P?
The ACV E-Tech P is a high-output floor-standing electric boiler designed for commercial and large-scale heating applications. It is available in five models from 57.6kW to 259.2kW.
Is the ACV E-Tech P a three-phase electric boiler?
Yes. The E-Tech P uses a 400V three-phase power circuit. Its control circuit uses 230V single-phase power.
What output sizes are available?
The range includes 57.6kW, 115.2kW, 144kW, 201.6kW and 259.2kW models.
Does the ACV E-Tech P require a flue?
No combustion flue is required because the E-Tech P is an electric boiler rather than a combustion appliance.
Can the E-Tech P be used as a backup boiler?
Yes. ACV describes the E-Tech P as suitable for use as a primary heat source or emergency backup.
Can multiple E-Tech P boilers be installed together?
Yes. ACV states that the E-Tech P can be used in multiple-boiler installations where higher combined output is required.
Is the E-Tech P suitable for domestic hot water?
The E-Tech P is a heat-only boiler. ACV states that it can be connected to external storage cylinders for domestic hot-water production where the system is designed accordingly.
Does the boiler include frost protection?
No. ACV states that the E-Tech P does not have integral frost protection. An appropriate external frost thermostat should be fitted where freezing conditions are possible.
Who should install an ACV E-Tech P?
Installation should be carried out by appropriately qualified heating and electrical professionals in accordance with the manufacturer’s instructions and applicable local regulations.
WATER HEATERS
Rinnai Water Heaters (Internal & External Installation)
Caravan Water Heaters
Commercial Continuous Flow Gas Water Heaters
Domestic Tankless Multipoint Gas Water Heaters
Gas Heaters Europe
Calor Gas Heaters
Gas Space Heaters
Warm Air Heaters Europe
Gas Warm Air Heaters
Electric Warm Air Heaters
Boilers Europe
Gas Boilers
ATAG Boilers Europe
Combi Boilers UK
System Boilers UK
Hot Water Cylinders Europe
Thermal Store Hot Water Cylinders
Unvented Hot Water Cylinders
Vented Hot Water Cylinders
Commercial Hot Water Cylinders
Air Conditioning & Air Purification
Air purifiers UK
Humidifiers UK
Dehumidifiers UK
Shipping Containers Europe
High Cube Containers
Standard Containers (20ft, 40ft)
Modified / Custom Containers
Refrigerated Containers
Storage Containers
Renewable Energy Europe
HOME HEATING OIL TANKS
Bunded Oil Tanks
Adblue Tanks
Fire Protected Oil Tanks
Fuel Bank Or Fuel Station Oil Tanks
Single Skinned oil Tanks
Secure Storage Europe
Smokeless Coal Europe
Firewood Europe
Briquettes & Heat Logs
WOOD PELLETS


Reviews
Clear filtersThere are no reviews yet.